Product Description
The instrument is a precision AC energy meter testing instrument, mainly used to test three phase energy meter error on site and measure various of AC parameters.
Features and Functions
w Three phase active or reactive electricity energy meter;
w Calibrate three phase, single phase, active or reactive meter error;
w Measure U(voltage) of three phase or single phase;
w Measure I(current) of three phase or single phase;
w Measure active power of three phase or single phase;
w Measure reactive power of three phase or single phase;
w Measure apparent power of three phase or single phase;
w Measure power factor of three phase or single phase;
w Measure phase angle between voltage and current;
w Measure frequency of power line;
w Display vector diagram;
w Display waveform of U and I;
w Analyze and display content of harmonic of U and I;
w Store and look measured data;
w Optional 5 A, 20 A, 100 A, 500 A, 1000 A, 2000 A current clamp;
w Measure CT variable ratio;
w Measure the ratio or lag-angle of low-voltage transformer.
w Print the data of measurement on site;
w Adopt 32 bit ARM processor, multi-channel 16 bit precision A/D convertor, high resolution TFT LCD;
w Inner equipped with 0.01% wide-range current transformer and can be equipped with various type current clamps, wide range of measurement and high veracity.
w Low consumption circuit design, high energy Li batter supply, intellectual power management software, which make the instrument can continuously work up to 10 hours.
Specification
Test Voltage
|
Range
|
5V – 480V
|
Error
|
±0.05% (30V – 480V)
±0.1% (5V – 30V)
|
Harmonic
|
2nd -- 63st
|
Test Current
|
Range (direct connection)
|
5mA – 20A
|
Error (direct connection)
|
±0.05% (100mA – 20A)
±0.1% (10mA – 100mA)
|
Harmonic
|
2nd -- 63st
|
Power measure error
|
Active power (direct connection)
|
±0.05% (0.1A – 20A)
±0.1% (0.01A – 0.1A)
|
Reactive power (direct connection)
|
±0.1% (0.1A – 20A)
|
Energy measure error
|
Active energy (direct connection)
|
±0.05% (0.1A – 20A)
±0.1% (0.01A – 0.1A)
|
Reactive energy (direct connection)
|
±0.1% (0.1A – 20A)
|
Phase angle
|
Range
|
0º – 360º
|
Error
|
±0.05º
|
Frequency
|
Range
|
45Hz – 65Hz
|
Pulse output
|
High frequency output(CH)
|
1×1011 (1mA – 10mA)
1×1010 (10mA – 0.1A)
1×109 (0.1A – 1.0A)
1×108 (1.0A – 10A)
1×107 (10A – 120A)
|
Low frequency output(CL)
|
2×10-5×CH
|
Pulse ratio
|
1:1
|
Output level
|
5V
|
Pulse input
|
Input channel
|
1
|
Input level
|
5 – 24V
|
Input frequency
|
Max. 2MHz
|
Display
|
Resolution
|
6”TFT (640×480)
|
Function
|
Vector diagram
|
●
|
Waveform
|
●
|
Energy accumulation
|
●
|
Communication port
|
RS232
|
Communication with PC
|
●
|
Other
|
Voltage Supply way
|
External power
|
Voltage Supply 1
|
220V ± 10%, 50/60Hz ± 2Hz
|
Voltage Supply 2
|
Li-polymer battery, size: 110X51X16mm
Nominal output voltage: 7.2V,Capacity: 5000mAh.
|
Ambient temperature
|
-10°C -- 55°C
|
Relative humidity
|
15% -- 85%
|
Instrument Dimensions (W×H×D) (mm)
|
245×162×60
|
Carry Case Dimensions (W×H×D) (mm)
|
450×320×185
|
Weight (kg)
|
1.7kg
|